    Safety Barrier

    This isolated barrier is used for intrinsic safety applications.

    The device supplies 2-wire and 3-wire SMART transmitters, and can also be used with 2-wire SMART current sources.

    It transfers the analog input signal to the safe area as an isolated current value.

    Digital signals may be superimposed on the input signal in the hazardous or non-hazardous area and are transferred bi-directionally.

    The device provides a sink mode or a source mode output on the safe area terminals.

    The device has an internal resistor. Use this resistor if the HART communication resistance in the control circuit is too low.

    Test sockets for the connection of HART communicators are integrated into the terminals of the device.

    It supports HART, Foxboro, BRAIN.

    share:

    Product Description
    Signal typeAnalog input
    Safety Integrity Level (SIL)SIL 2
    Systematic capability (SC)SC 3
    ConnectionPower Rail or terminals 14+, 15-
    Rated voltageUr18 ... 30 V DC
    Ripplewithin the supply tolerance
    Power dissipation≤ 1.4 W at maximum load
    Power consumption≤ 2.6 W at maximum load
    Connection sidefield side
    Connectionterminals 1+, 2-, 3; 4+, 5-, 6
    Input signal4 ... 20 mA
    Open circuit voltage/short-circuit currentterminals 1+, 3; 4+, 6: 23 V / 25 mA
    Input resistancemax. 265 Ω terminals 2-, 3; 5-, 6 , max. 330 Ω terminals 1+, 3; 4+, 6
    Available voltage≥ 16 V at 20 mA ; ≥ 20 V at 4 mA , terminals 1+, 3; 4+, 6