    Flow sensors

    non-contact FFU ultrasonic flowmeter flow volume of conductive and non-conductive liquids Similar products FFUS10-1N1IO Part no.: 6047868 FFUC25-1N1SR Part no.: 6056879 FFUS20-1N1IO Part no.: 6047870 FFUS15-1N1IO Part no.: 6047869 FFUC50-3G1IO Part no.: 6072920 FFUC25-1G1IO Part no.: 6049019 FFUC25-3G1IO Part no.: 6075523 FFUS25-1C1IO Part no.: 6044523 FFUS15-1N1SR Part no.: 6060235 FFUC20-1N1IO Part no.: 6058038 FFUC15-1G1IO Part no.: 6049017 FFUS25-1C1SR Part no.: 6052255 FFUS15-1G1IO Part no.: 6041249 FFUC10-1G1IO Part no.: 6049016 FFUC20-1G1IO Part no.: 6049018 FFUS25-1N1SR Part no.: 6049566 FFUS20-1G1SR Part no.: 6043745 FFUS25-1G1SR Part no.: 6043746 FFUS10-1C1SR Part no.: 6066448 FFUS25-1N1IO Part no.: 6044996 FFUC25-1C1SR Part no.: 6050188 FFUS25-1G1IO Part no.: 6041739 FFUS20-1C1IO Part no.: 6049061 FFUS10-1N1SR Part no.: 6050786 FFUC32-3G1IO Part no.: 6072918 FFUC10-1C1SR Part no.: 6053120 FFUS10-1G1IO Part no.: 6041737 FFUC10-1G1SR Part no.: 6052236 FFUC40-3G1IO Part no.: 6072919 FFUS10-1G1SR Part no.: 6043743 FFUS15-1G1SR Part no.: 6043744 FFUS20-1G1IO Part no.: 6041738 FFUS20-1N1SR Part no.: 6058219 FFUS15-1C1IO Part no.: 6045162 FFUC10-1N1IO Part no.: 6058261 FFUS10-1C1IO Part no.: 6049101 FFUC20-1C1SR Part no.: 6053121 FFUS15-1C1SR Part no.: 6066449 FFUC15-1C1SR Part no.: 6050189 FFUC25-1G1SR Part no.: 6052239 FFUS20-1C1SR Part no.: 6059009 FFUC25-1N1IO Part no.: 6054505 FFUC20-1G1SR Part no.: 6052238 FFUC15-1G1SR Part no.: 6052237

    share:

    Product Description
    Minimum flow≥ 0.3 l/min 1)
    Maximum flow≤ 21 l/min
    Inlet zone10 cm
    Output zone0 cm
    ConductivityNo limitation
    Measurement accuracy± 2 % of measured value + 0.15% of measuring range limit value 2)
    Repeatability≤ 0.5 %
    Resolution0.003 l/min
    Response time100 ms 3)300 ms 3)1 s 3)4.2 s 3)
    Measurement principleUltrasonic sensor
    MediumFluids
    Nominal width measuring tubeDN 10
    Process temperature0 °C ... +80 °C
    Process pressure≤ 16 bar
    Communication interface-
    Supply voltage18 V DC ... 30 V DC 1)
    Residual ripple≤ 5 Vpp 2)
    Power consumption≤ 180 mA 3)
    Switch-on time≤ 5 s
    Protection class
    Connection typeRound connector M12 x 1, 5-pin
    Output signalAnalog output 4 mA ... 20 mA, 0 mA ... 20 mA current flow and temperature 1)1 pulse/status output PNP/NPN-transistor output for flow rate meter, empty pipe detection, flow monitoring, dosing output, flow direction (dependent on type)
    Output current< 100 mA 4)
    Output load< 500 Ohm
    Lower signal level3.8 mA ... 4 mA
    Upper signal level20 mA ... 20.5 mA
    Impuls/frequency output0 kHz ... 10 kHz
    Puls width≤ 1 s
    Inductive load1 H
    Capacitive load100 nF
    Enclosure ratingIP67